British Columbia Fire Watch Course 2026
This course is for security guards in British Columbia who are posted on a fire watch while a fire alarm or sprinkler system is out of service, or during hot work. It covers the BC Fire Code and Fire Safety Act, local rules from Vancouver and Chilliwack, the fire watch log, and hot work.
Kort antwoord
Deze gratis cursus heeft ongeveer 20 minuten lessen en een toets van 25 vragen. Haal 80% of meer om een bewijs van deelname te downloaden (privé, niet geaccrediteerd). Gecontroleerd aan de hand van officiële bronnen op 12 oktober 2026.
Wat je leert
- Name the BC fire laws and who enforces them
- Explain when the Fire Code calls for alternative measures such as a fire watch
- Apply local fire watch rules from BC fire departments
- Keep a fire watch log that meets a BC fire department's order
- Follow the minimum hot work fire watch rules in the BC Fire Code text
Haal 80% of meer om je certificaat te downloaden.
-
Vraag 1 van 25
Toon antwoord
Antwoord: D. The BC Fire Code 2024
The BC Fire Code 2024 is the current edition, administered and enforced by the Office of the Fire Commissioner.
-
Vraag 2 van 25
Toon antwoord
Antwoord: A. March 8, 2024
The Ministerial Order adopting the BC Fire Code 2024 took effect on March 8, 2024.
-
Vraag 3 van 25
Toon antwoord
Antwoord: C. The National Fire Code 2020
The order adopts Divisions A to C of the National Fire Code of Canada 2020 as the BC Fire Code, with BC amendments.
-
Vraag 4 van 25
Toon antwoord
Antwoord: C. The Office of the Fire Commissioner
The province says the Office of the Fire Commissioner is responsible for administering and enforcing the BC Fire Code.
-
Vraag 5 van 25
Toon antwoord
Antwoord: B. The Fire Safety Act
The province says the Fire Safety Act replaced the Fire Services Act as of August 1, 2024.
-
Vraag 6 van 25
Toon antwoord
Antwoord: C. The local authority, like a council
The Act defines a fire inspector as an individual designated by a local authority under section 8.
-
Vraag 7 van 25
Toon antwoord
Antwoord: C. That no fire hazard exists there
Section 7 says an owner must ensure that no fire hazard exists on or in the owner's premises.
-
Vraag 8 van 25
Toon antwoord
Antwoord: B. Report it at once to the fire department
Section 22 says the occupier, or the owner if there is none, must immediately report the fire to a fire department or the fire commissioner when no fire department attended.
-
Vraag 9 van 25
Toon antwoord
Antwoord: B. Alternative measures must be taken
Article 6.1.1.4 of the 2018 BC Fire Code text says alternative measures shall be taken during a shutdown to maintain protection.
-
Vraag 10 van 25
Toon antwoord
Antwoord: B. Extra fire watch service
The note for sprinkler shutdowns lists emergency hose lines, portable extinguishers, extra fire watch service and temporary water connections.
-
Vraag 11 van 25
Toon antwoord
Antwoord: A. With the fire department
The note says alternative measures for a fire alarm shutdown should be worked out in cooperation with the fire department.
-
Vraag 12 van 25
Toon antwoord
Antwoord: A. Through its own Fire By-law
Vancouver's Fire By-law No. 14419 adopts the BC Fire Code with the city's own changes.
-
Vraag 13 van 25
Toon antwoord
Antwoord: D. If out over 4 hours in a row in 24 hours
Vancouver asks owners to call 3-1-1 (in business hours) when a system is out more than 4 continuous hours in a 24-hour period, and again when it is back.
-
Vraag 14 van 25
Toon antwoord
Antwoord: C. Every 60 minutes
The order sets a minimum of every 30 minutes in business hours and every 60 minutes at other times for non-residential buildings.
-
Vraag 15 van 25
Toon antwoord
Antwoord: C. When it goes out and when it returns
The order requires notice to the central station when the system goes out and when it is back in service.
-
Vraag 16 van 25
Toon antwoord
Antwoord: A. At the main entrance and other key points
The order must be posted at the main entrance, with copies at other main access points, inside elevators and stairs, and at every tenancy.
-
Vraag 17 van 25
Toon antwoord
Antwoord: B. Names and locations of those needing help
The order asks whether anyone with a disability needs help and says to record their names and locations in the log.
-
Vraag 18 van 25
Toon antwoord
Antwoord: B. At least every 15 minutes
Chilliwack requires patrols at least every 15 minutes during sleeping hours, 9 pm to 8 am.
-
Vraag 19 van 25
Toon antwoord
Antwoord: A. A dedicated person who only looks for fires
Chilliwack says a fire watch is a dedicated person on site whose sole duty is to actively look for fires.
-
Vraag 20 van 25
Toon antwoord
Antwoord: A. At entrances, exits and elevators
Chilliwack asks for signs at all entrances, exits and elevators on each floor stating that a fire watch is in effect and its expected duration.
-
Vraag 21 van 25
Toon antwoord
Antwoord: B. An ASTTBC fire protection technician
Chilliwack says the owner should contact a qualified ASTTBC fire protection technician, who should notify the fire department.
-
Vraag 22 van 25
Toon antwoord
Antwoord: D. Not a substitute for repairing it
Chilliwack states that temporary measures such as a fire watch are not a substitute for repairing the system.
-
Vraag 23 van 25
Toon antwoord
Antwoord: D. At least 60 minutes
Article 5.2.3.1 of the 2018 BC Fire Code text requires a continuous fire watch for not less than 60 minutes after hot work is completed.
-
Vraag 24 van 25
Toon antwoord
Antwoord: D. 4 hours after the work
Article 5.2.3.1 of the 2018 BC Fire Code text requires an inspection 4 hours after completion, or a more thorough one when the fire watch ends.
-
Vraag 25 van 25
Toon antwoord
Antwoord: C. In the building
Article 2.8.2.5 of the 2018 BC Fire Code text says the fire safety plan must be kept in the building for reference by the fire department.
Toetsenbord: 1–4 om te antwoorden, Enter voor de volgende vraag.
Wat je moet weten voor het examen
- The BC Fire Code 2024 adopts the National Fire Code of Canada 2020 with BC changes and took effect on March 8, 2024.
- The Office of the Fire Commissioner administers and enforces the BC Fire Code.
- BC's Fire Safety Act replaced the Fire Services Act on August 1, 2024.
- Vancouver asks owners to call 3-1-1 if a fire protection system is out for more than 4 continuous hours in 24 hours.
- Chilliwack requires fire watch patrols at least every 15 minutes from 9 pm to 8 am in buildings where people sleep.
Veelgestelde vragen
Who enforces fire rules in British Columbia?
The Office of the Fire Commissioner administers and enforces the BC Fire Code. Local governments designate fire inspectors under the Fire Safety Act, and Vancouver uses its own Fire By-law.
How often do I patrol on a fire watch in BC?
It depends on the local fire department. Vancouver and Chilliwack both ask for rounds every 15 minutes overnight in buildings where people sleep, and every 30 to 60 minutes in other cases.
Do I need to call the fire department when an alarm goes out?
Follow your local rules. In Vancouver, owners call 3-1-1 if a system is out more than 4 continuous hours in 24 hours. In Chilliwack, the fire protection technician notifies the fire department.
How long does a hot work fire watch last in BC?
The hot work section of the 2018 BC Fire Code text requires a continuous fire watch for at least 60 minutes after the work ends, and an inspection 4 hours after. Check the current code and your hot work permit.
Is het certificaat geaccrediteerd of officieel erkend?
Nee. Het is een privé bewijs van deelname, alleen voor je kennis. Het is niet erkend, geaccrediteerd of goedgekeurd door een overheid, vergunningsinstantie, toezichthouder of onderwijsinstelling, en het vervangt geen wettelijk verplichte vergunning, certificering of opleiding.
Bronnen
- Government of BC: BC Fire Code
- Ministerial Order adopting the BC Fire Code 2024
- Fire Safety Act, SBC 2016, c. 19 (BC Laws)
- BC Fire Code (2018 text), Division B, Section 6.1 and Part 6 notes
- BC Fire Code (2018 text), Division B, Section 5.2 Hot Work
- City of Vancouver: Fire watch order
- City of Chilliwack: Fire watch
- City of Chilliwack: Fire protection equipment out of service