Fire Watch Course for Security Officers (US) 2026
This course is for security officers in the United States who may be posted on a fire watch while a fire alarm or sprinkler system is out of service, or during hot work. It covers fire code section 901.7, patrol rounds, the log, hot work and what to do if you find fire, with examples from New York, North Carolina, Ohio and Texas. It is background knowledge only: some places, such as New York City, require a fire guard certificate of their own.
Kort svar
Den här gratiskursen har lektioner på cirka 30 minuter och ett prov med 25 frågor. Med minst 80 % kan du ladda ner ett kursintyg (privat, inte ackrediterat). Kontrollerad mot officiella källor den 13 oktober 2026.
Det här lär du dig
- Explain what fire code section 901.7 requires when a system is out of service
- Prepare the right equipment and building information for a fire watch
- Patrol at the frequency your fire department sets and spot hazards
- Keep a complete and honest fire watch log
- Respond in the right order if you find fire or smoke
- Apply OSHA hot work fire watch rules
- Describe how a fire watch is properly ended
Få minst 80 % för att ladda ner ditt certifikat.
-
Fråga 1 av 25
Visa svar
Svar: A. The fire department and the fire code official
Section 901.7 of the International Fire Code, adopted in places such as New York State, says the fire department and the fire code official must be notified immediately.
-
Fråga 2 av 25
Visa svar
Svar: D. Evacuate the building or provide an approved fire watch
Under section 901.7, the fire code official may require the building to be evacuated or an approved fire watch to be provided until the system is back in service.
-
Fråga 3 av 25
Visa svar
Svar: D. A temporary measure for steady, systematic watching of a building
The code definition calls a fire watch a temporary measure for continuous and systematic surveillance of a building, to find hazards and early signs of fire and raise the alarm.
-
Fråga 4 av 25
Visa svar
Svar: A. The building owner
The owner must assign an impairment coordinator. If no one is named, the owner is the impairment coordinator.
-
Fråga 5 av 25
Visa svar
Svar: B. A tag that shows the system is out of service
Section 901.7.2 requires a tag to show that a system, or part of it, has been removed from service. Tags go at places such as control valves and the fire alarm control unit.
-
Fråga 6 av 25
Visa svar
Svar: B. Fire guards holding an FDNY F-01 Certificate of Fitness
FDNY says that after the first 4 hours, impairment patrols may only be done by fire guards holding a Certificate of Fitness (F-01, Citywide Fire Guard for Impairment).
-
Fråga 7 av 25
Visa svar
Svar: C. To do constant patrols and keep watch for fires
Section 901.7, as adopted in Ohio and North Carolina, says the fire watch's only duty is to perform constant patrols of the premises and keep watch for fires.
-
Fråga 8 av 25
Visa svar
Svar: C. At least one approved way to notify the fire department
Section 901.7 requires each fire watch person to have at least one approved means of notifying the fire department, such as a phone or radio that reaches 911.
-
Fråga 9 av 25
Visa svar
Svar: D. Buildings where people sleep
Brunswick County requires 15-minute rounds where people sleep, in institutional buildings and in occupied assembly buildings, because people there may be slow to notice a fire.
-
Fråga 10 av 25
Visa svar
Svar: B. At least every 60 minutes
Brunswick County requires every area to be observed at least hourly, so buildings that do not need 15-minute rounds are patrolled every 60 minutes.
-
Fråga 11 av 25
Visa svar
Svar: A. Every 30 minutes
Miami Township sets rounds every 30 minutes in unoccupied buildings and every 15 minutes where people may be asleep.
-
Fråga 12 av 25
Visa svar
Svar: B. 50,000 square feet
FDNY says no fire guard may patrol more than 50,000 square feet of floor area. Larger buildings need more guards.
-
Fråga 13 av 25
Visa svar
Svar: D. At least once every hour
FDNY says the entire building must be checked at least once every hour during an impairment fire watch.
-
Fråga 14 av 25
Visa svar
Svar: B. Blocked exits and other hazards
Richardson's fire watch duties include a diligent watch for fires, obstructions to exits and other hazards.
-
Fråga 15 av 25
Visa svar
Svar: D. Exit routes must be kept free and unobstructed
OSHA 29 CFR 1910.37 says exit routes must be free and unobstructed, and no materials may be placed in them, even for a short time. Report it right away.
-
Fråga 16 av 25
Visa svar
Svar: A. The time each patrol tour was completed
The log must show the facility address, the time each tour was completed, the name of the fire watch person and other details the fire department asks for.
-
Fråga 17 av 25
Visa svar
Svar: B. The fire department and the monitoring company
The log must include a record of communications with the fire department and the alarm monitoring company.
-
Fråga 18 av 25
Visa svar
Svar: C. On site, ready for the fire code official to inspect
Miami Township, Ohio, and McDowell County, North Carolina, say the fire watch log is kept on site so the fire department or fire code official can review it.
-
Fråga 19 av 25
Visa svar
Svar: A. Call 911 with no delay
FDNY teaches fire guards to call 911 first, with no delay, and then sound the alarm and notify the person in charge.
-
Fråga 20 av 25
Visa svar
Svar: B. Do not assume the fire department has been called
FDNY warns fire guards not to assume the fire department has been called just because an alarm or smoke detector sounds.
-
Fråga 21 av 25
Visa svar
Svar: D. People on the fire floor and the floor above
FDNY says occupants on the fire floor and the floor above leave first, using the stairs rather than elevators.
-
Fråga 22 av 25
Visa svar
Svar: C. Only when the fire is clearly small enough for the equipment
OSHA 29 CFR 1910.252 says fire watchers try to put out a fire only when it is obviously within the capacity of the equipment available. Otherwise they sound the alarm.
-
Fråga 23 av 25
Visa svar
Svar: B. 35 feet
Under 29 CFR 1910.252, a fire watch is required when appreciable combustible material is closer than 35 feet to the welding or cutting, among other conditions.
-
Fråga 24 av 25
Visa svar
Svar: A. At least half an hour
OSHA 29 CFR 1910.252 requires the fire watch to stay for at least half an hour after welding or cutting is finished, to catch smoldering fires.
-
Fråga 25 av 25
Visa svar
Svar: D. The system is tested and the fire department and others are told
When a system is restored, the impairment coordinator makes sure it is inspected and tested, notifies the fire department and other parties, and then removes the tag.
Tangentbord: 1–4 för att svara, Enter för nästa fråga.
Bra att veta före provet
- Under fire code section 901.7, the fire department and the fire code official must be notified right away when a required fire protection system is out of service.
- The fire code official may require the building to be evacuated or an approved fire watch to be provided until the system is back in service.
- Patrol frequency is set locally. Brunswick County, North Carolina, asks for rounds every 15 minutes where people sleep and every 60 minutes in other buildings.
- In New York City, after the first 4 hours of an outage, impairment patrols must be done by fire guards holding an FDNY F-01 Certificate of Fitness.
- OSHA requires a hot work fire watch to continue for at least half an hour after welding or cutting is finished.
Vanliga frågor
What does a fire watch officer do?
They patrol the affected building on a set schedule, look for fire and hazards such as blocked exits, keep a log, and call 911 and warn occupants if they find fire or smoke. Many fire codes say patrolling is their only duty.
How often do I patrol on a fire watch?
Your fire department or permit sets it. Examples include every 15 minutes where people sleep and every 60 minutes elsewhere in Brunswick County, North Carolina, and a full check of the building at least every hour in New York City.
Do I need a certificate to work a fire watch?
It depends on where you work. New York City requires an FDNY F-01 Certificate of Fitness for impairment fire guards after the first 4 hours, and your state may also require a security guard license. This course is background knowledge only and does not replace any required certificate or training.
How long does a fire watch after welding last?
OSHA requires at least half an hour after welding or cutting ends. Follow your hot work permit or local code if it sets a longer time.
Är intyget ackrediterat eller officiellt erkänt?
Nej. Det är ett privat kursintyg, bara för dina kunskaper. Det är inte erkänt, ackrediterat eller godkänt av någon myndighet, tillståndsmyndighet, tillsynsmyndighet eller utbildningsinstitution, och det ersätter inte någon licens, certifiering eller utbildning som krävs enligt lag.
Källor
- City of Syracuse Fire Department: Code requirements for systems out of service (Fire Code of New York State 901.7)
- City of Kerrville Fire Marshal: Fire watch (IFC 901.7)
- Brunswick County, NC Fire Marshal: Fire watch requirements
- Miami Township, OH Fire & EMS: Fire watch requirements
- City of Missouri City, TX: Fire watch requirements
- FDNY: Certificate of Fitness F-01 (Citywide Fire Guard for Impairment)
- FDNY: F-01 study material
- OSHA 29 CFR 1910.252: Welding, cutting and brazing (fire prevention)