Fire Watch Course for Security Officers (US) 2026
This course is for security officers in the United States who may be posted on a fire watch while a fire alarm or sprinkler system is out of service, or during hot work. It covers fire code section 901.7, patrol rounds, the log, hot work and what to do if you find fire, with examples from New York, North Carolina, Ohio and Texas. It is background knowledge only: some places, such as New York City, require a fire guard certificate of their own.
Kort antwoord
Deze gratis cursus heeft ongeveer 30 minuten lessen en een toets van 25 vragen. Haal 80% of meer om een bewijs van deelname te downloaden (privé, niet geaccrediteerd). Gecontroleerd aan de hand van officiële bronnen op 13 oktober 2026.
Wat je leert
- Explain what fire code section 901.7 requires when a system is out of service
- Prepare the right equipment and building information for a fire watch
- Patrol at the frequency your fire department sets and spot hazards
- Keep a complete and honest fire watch log
- Respond in the right order if you find fire or smoke
- Apply OSHA hot work fire watch rules
- Describe how a fire watch is properly ended
Haal 80% of meer om je certificaat te downloaden.
-
Vraag 1 van 25
Toon antwoord
Antwoord: A. The fire department and the fire code official
Section 901.7 of the International Fire Code, adopted in places such as New York State, says the fire department and the fire code official must be notified immediately.
-
Vraag 2 van 25
Toon antwoord
Antwoord: D. Evacuate the building or provide an approved fire watch
Under section 901.7, the fire code official may require the building to be evacuated or an approved fire watch to be provided until the system is back in service.
-
Vraag 3 van 25
Toon antwoord
Antwoord: D. A temporary measure for steady, systematic watching of a building
The code definition calls a fire watch a temporary measure for continuous and systematic surveillance of a building, to find hazards and early signs of fire and raise the alarm.
-
Vraag 4 van 25
Toon antwoord
Antwoord: A. The building owner
The owner must assign an impairment coordinator. If no one is named, the owner is the impairment coordinator.
-
Vraag 5 van 25
Toon antwoord
Antwoord: B. A tag that shows the system is out of service
Section 901.7.2 requires a tag to show that a system, or part of it, has been removed from service. Tags go at places such as control valves and the fire alarm control unit.
-
Vraag 6 van 25
Toon antwoord
Antwoord: B. Fire guards holding an FDNY F-01 Certificate of Fitness
FDNY says that after the first 4 hours, impairment patrols may only be done by fire guards holding a Certificate of Fitness (F-01, Citywide Fire Guard for Impairment).
-
Vraag 7 van 25
Toon antwoord
Antwoord: C. To do constant patrols and keep watch for fires
Section 901.7, as adopted in Ohio and North Carolina, says the fire watch's only duty is to perform constant patrols of the premises and keep watch for fires.
-
Vraag 8 van 25
Toon antwoord
Antwoord: C. At least one approved way to notify the fire department
Section 901.7 requires each fire watch person to have at least one approved means of notifying the fire department, such as a phone or radio that reaches 911.
-
Vraag 9 van 25
Toon antwoord
Antwoord: D. Buildings where people sleep
Brunswick County requires 15-minute rounds where people sleep, in institutional buildings and in occupied assembly buildings, because people there may be slow to notice a fire.
-
Vraag 10 van 25
Toon antwoord
Antwoord: B. At least every 60 minutes
Brunswick County requires every area to be observed at least hourly, so buildings that do not need 15-minute rounds are patrolled every 60 minutes.
-
Vraag 11 van 25
Toon antwoord
Antwoord: A. Every 30 minutes
Miami Township sets rounds every 30 minutes in unoccupied buildings and every 15 minutes where people may be asleep.
-
Vraag 12 van 25
Toon antwoord
Antwoord: B. 50,000 square feet
FDNY says no fire guard may patrol more than 50,000 square feet of floor area. Larger buildings need more guards.
-
Vraag 13 van 25
Toon antwoord
Antwoord: D. At least once every hour
FDNY says the entire building must be checked at least once every hour during an impairment fire watch.
-
Vraag 14 van 25
Toon antwoord
Antwoord: B. Blocked exits and other hazards
Richardson's fire watch duties include a diligent watch for fires, obstructions to exits and other hazards.
-
Vraag 15 van 25
Toon antwoord
Antwoord: D. Exit routes must be kept free and unobstructed
OSHA 29 CFR 1910.37 says exit routes must be free and unobstructed, and no materials may be placed in them, even for a short time. Report it right away.
-
Vraag 16 van 25
Toon antwoord
Antwoord: A. The time each patrol tour was completed
The log must show the facility address, the time each tour was completed, the name of the fire watch person and other details the fire department asks for.
-
Vraag 17 van 25
Toon antwoord
Antwoord: B. The fire department and the monitoring company
The log must include a record of communications with the fire department and the alarm monitoring company.
-
Vraag 18 van 25
Toon antwoord
Antwoord: C. On site, ready for the fire code official to inspect
Miami Township, Ohio, and McDowell County, North Carolina, say the fire watch log is kept on site so the fire department or fire code official can review it.
-
Vraag 19 van 25
Toon antwoord
Antwoord: A. Call 911 with no delay
FDNY teaches fire guards to call 911 first, with no delay, and then sound the alarm and notify the person in charge.
-
Vraag 20 van 25
Toon antwoord
Antwoord: B. Do not assume the fire department has been called
FDNY warns fire guards not to assume the fire department has been called just because an alarm or smoke detector sounds.
-
Vraag 21 van 25
Toon antwoord
Antwoord: D. People on the fire floor and the floor above
FDNY says occupants on the fire floor and the floor above leave first, using the stairs rather than elevators.
-
Vraag 22 van 25
Toon antwoord
Antwoord: C. Only when the fire is clearly small enough for the equipment
OSHA 29 CFR 1910.252 says fire watchers try to put out a fire only when it is obviously within the capacity of the equipment available. Otherwise they sound the alarm.
-
Vraag 23 van 25
Toon antwoord
Antwoord: B. 35 feet
Under 29 CFR 1910.252, a fire watch is required when appreciable combustible material is closer than 35 feet to the welding or cutting, among other conditions.
-
Vraag 24 van 25
Toon antwoord
Antwoord: A. At least half an hour
OSHA 29 CFR 1910.252 requires the fire watch to stay for at least half an hour after welding or cutting is finished, to catch smoldering fires.
-
Vraag 25 van 25
Toon antwoord
Antwoord: D. The system is tested and the fire department and others are told
When a system is restored, the impairment coordinator makes sure it is inspected and tested, notifies the fire department and other parties, and then removes the tag.
Toetsenbord: 1–4 om te antwoorden, Enter voor de volgende vraag.
Wat je moet weten voor het examen
- Under fire code section 901.7, the fire department and the fire code official must be notified right away when a required fire protection system is out of service.
- The fire code official may require the building to be evacuated or an approved fire watch to be provided until the system is back in service.
- Patrol frequency is set locally. Brunswick County, North Carolina, asks for rounds every 15 minutes where people sleep and every 60 minutes in other buildings.
- In New York City, after the first 4 hours of an outage, impairment patrols must be done by fire guards holding an FDNY F-01 Certificate of Fitness.
- OSHA requires a hot work fire watch to continue for at least half an hour after welding or cutting is finished.
Veelgestelde vragen
What does a fire watch officer do?
They patrol the affected building on a set schedule, look for fire and hazards such as blocked exits, keep a log, and call 911 and warn occupants if they find fire or smoke. Many fire codes say patrolling is their only duty.
How often do I patrol on a fire watch?
Your fire department or permit sets it. Examples include every 15 minutes where people sleep and every 60 minutes elsewhere in Brunswick County, North Carolina, and a full check of the building at least every hour in New York City.
Do I need a certificate to work a fire watch?
It depends on where you work. New York City requires an FDNY F-01 Certificate of Fitness for impairment fire guards after the first 4 hours, and your state may also require a security guard license. This course is background knowledge only and does not replace any required certificate or training.
How long does a fire watch after welding last?
OSHA requires at least half an hour after welding or cutting ends. Follow your hot work permit or local code if it sets a longer time.
Is het certificaat geaccrediteerd of officieel erkend?
Nee. Het is een privé bewijs van deelname, alleen voor je kennis. Het is niet erkend, geaccrediteerd of goedgekeurd door een overheid, vergunningsinstantie, toezichthouder of onderwijsinstelling, en het vervangt geen wettelijk verplichte vergunning, certificering of opleiding.
Bronnen
- City of Syracuse Fire Department: Code requirements for systems out of service (Fire Code of New York State 901.7)
- City of Kerrville Fire Marshal: Fire watch (IFC 901.7)
- Brunswick County, NC Fire Marshal: Fire watch requirements
- Miami Township, OH Fire & EMS: Fire watch requirements
- City of Missouri City, TX: Fire watch requirements
- FDNY: Certificate of Fitness F-01 (Citywide Fire Guard for Impairment)
- FDNY: F-01 study material
- OSHA 29 CFR 1910.252: Welding, cutting and brazing (fire prevention)