PassEveryTest
العربية

New Brunswick Fire Watch Course 2026

This course is for security guards in New Brunswick who may be posted on a fire watch while a fire alarm or sprinkler system is out of service, or during hot work. It covers the province's fire law, the Office of the Fire Marshal's fire watch technotes, the sign-off sheet and hot work rules.

  • دورة
  • نيو برونزويك
  • عدد الأسئلة: 25
  • تمت المراجعة في 12 أكتوبر 2026

إجابة سريعة

تتضمن هذه الدورة المجانية نحو 30 دقيقة من الدروس واختبارًا يضم 25 من الأسئلة. احصل على 80% أو أكثر لتنزيل شهادة إتمام (خاصة، غير معتمدة). تمت مراجعته مقارنةً بالمصادر الرسمية في 12 أكتوبر 2026.

ابدأ بالدروسNew Brunswick Fire Watch Course: Lessons: نحو 30 دقيقة من القراءة. كل أسئلة الاختبار مشروحة في الدروس.

ما ستتعلمه

  • Name the fire law, code and officials that apply in New Brunswick
  • Explain when the Office of the Fire Marshal requires a fire watch
  • Carry out hourly fire watch patrols with the right tools
  • Keep an honest fire watch sign-off sheet
  • Apply the province's hot work fire watch rules
  • Respond safely if you find fire

احصل على 80% أو أكثر لتنزيل شهادتك.

  1. السؤال 1 من 25

    Which fire code edition is adopted in New Brunswick under the Fire Prevention and Inspection Regulation?
    أظهر الإجابة

    الإجابة: C. National Fire Code of Canada 2020

    Section 2(a) of Regulation 82-20 incorporates the National Fire Code of Canada 2020.

  2. السؤال 2 من 25

    Under which Act is New Brunswick's Fire Prevention and Inspection Regulation (82-20) made?
    أظهر الإجابة

    الإجابة: A. The Fire Prevention Act

    Regulation 82-20 is made under New Brunswick's Fire Prevention Act.

  3. السؤال 3 من 25

    According to the Office of the Fire Marshal's Bulletin 2025-01, when did the 2020 code amendments take effect in New Brunswick?
    أظهر الإجابة

    الإجابة: A. May 1, 2025

    Bulletin 2025-01 says the amended regulations, which adopt the 2020 National Fire Code and National Building Code, took effect May 1, 2025.

  4. السؤال 4 من 25

    Under section 6(1) of the Fire Prevention Act, who may the fire marshal appoint as a local assistant for their area?
    أظهر الإجابة

    الإجابة: B. A fire chief or other fire department member

    Section 6(1) of the Fire Prevention Act lets the fire marshal appoint the chief or another member of a fire department as a local assistant for that department's area.

  5. السؤال 5 من 25

    Under section 11 of the Fire Prevention Act, who may enter and inspect a building at reasonable hours?
    أظهر الإجابة

    الإجابة: A. Fire marshal, deputy, fire prevention officers or local assistants

    Section 11 gives the fire marshal, deputy fire marshal, fire prevention officers and local assistants the power to inspect buildings at reasonable hours.

  6. السؤال 6 من 25

    A tenant switches off a smoke detection system to stop it beeping, without written authorization. Under section 23 of the Fire Prevention Act, this is:
    أظهر الإجابة

    الإجابة: B. An offence, unless it is for maintenance and repairs

    Section 23(a.1) makes it an offence to tamper with exits, extinguishers, sprinklers, detection or alarm systems without written authorization, except for maintenance and repairs.

  7. السؤال 7 من 25

    Under section 23(a.2) of the Fire Prevention Act, what is it an offence to do without written authorization?
    أظهر الإجابة

    الإجابة: D. Block an exit or the way to an exit

    Section 23(a.2) makes it an offence to block an exit or an access to an exit, or remove an exit stair or fire escape, without written authorization.

  8. السؤال 8 من 25

    A building owner ignores a written order from a fire prevention officer to fix a hazard. Under the Fire Prevention Act, what is this?
    أظهر الإجابة

    الإجابة: D. An offence

    Section 24(1) of the Fire Prevention Act says an owner or occupant who fails to comply with an order commits an offence.

  9. السؤال 9 من 25

    Under Fire Technote 2006-09R, what kind of fire watch is required while a sprinkler or fire alarm system is being modified or renovated?
    أظهر الإجابة

    الإجابة: B. A dedicated, 24 hour per day fire watch

    Technote 2006-09R from the Office of the Fire Marshal requires a dedicated, 24 hour per day fire watch.

  10. السؤال 10 من 25

    Under Technote 2006-09R, who may provide the fire watch?
    أظهر الإجابة

    الإجابة: D. One or more persons whose only job is the fire watch

    The technote says the fire watch is done by one or more persons whose only job function is providing the fire watch.

  11. السؤال 11 من 25

    How often does Technote 2006-09R say the fire watch must patrol the areas where the alarm or sprinklers are not working?
    أظهر الإجابة

    الإجابة: C. Hourly

    Technote 2006-09R requires hourly patrols of the areas where the fire alarm or sprinkler system is not operational.

  12. السؤال 12 من 25

    Under Technote 2006-09R, how is each fire watch patrol recorded?
    أظهر الإجابة

    الإجابة: B. On a sign-off sheet with the time of each patrol

    Each patrol is recorded on a sign-off sheet that shows the patrol was done and the time it was done.

  13. السؤال 13 من 25

    Which tool must a fire watch person have under Technote 2006-09R?
    أظهر الإجابة

    الإجابة: A. A way to call 911 right away

    The technote requires the fire watch to have a means to immediately contact 911 services.

  14. السؤال 14 من 25

    Under Technote 2006-09R, who is responsible for notifying building occupants during a fire watch?
    أظهر الإجابة

    الإجابة: D. The fire watch person or persons

    The fire watch must have a means of contacting building occupants and is responsible for notifying them.

  15. السؤال 15 من 25

    Which plan must the fire watch person know and understand under Technote 2006-09R?
    أظهر الإجابة

    الإجابة: D. The construction fire safety plan

    Technote 2006-09R says the fire watch must know the construction fire safety plan and understand their responsibilities in it.

  16. السؤال 16 من 25

    What training must a fire watch person have under Technote 2006-09R?
    أظهر الإجابة

    الإجابة: D. Training in how to use a fire extinguisher

    The technote requires the fire watch to be trained in the use of a fire extinguisher.

  17. السؤال 17 من 25

    During a fire alarm contractor's work day, Technote 2006-07R says no fire watch is needed if any sprinkler system stays fully working and monitored, and what else is true?
    أظهر الإجابة

    الإجابة: D. The contractor's staff are always in the affected area

    Technote 2006-07R allows no fire watch during the contractor's work day only if the affected area is constantly occupied by their staff and any sprinkler system stays fully operational and monitored.

  18. السؤال 18 من 25

    A fire alarm contractor goes home, but the alarm system is still not fully working. What does Technote 2006-07R require?
    أظهر الإجابة

    الإجابة: B. A dedicated fire watch

    If the fire alarm system is not fully functional at the end of the contractor's work day, a dedicated fire watch is required.

  19. السؤال 19 من 25

    During sprinkler work, Technote 2006-08R says no fire watch is needed in the contractor's work day if the affected area is occupied by their staff and what else is true?
    أظهر الإجابة

    الإجابة: A. The fire alarm works everywhere, including the work area

    Technote 2006-08R requires the fire alarm system to be fully functional throughout the building, including the work area.

  20. السؤال 20 من 25

    Under the Fire Marshal's hot work bulletin, how long must a fire watch continue after hot work is finished?
    أظهر الإجابة

    الإجابة: D. 60 minutes

    Bulletin 2001-16 requires a fire watch during hot work and for 60 minutes after it is completed.

  21. السؤال 21 من 25

    Under the hot work bulletin, when must the hot work area be inspected after the work is finished?
    أظهر الإجابة

    الإجابة: A. 4 hours after the work is finished

    Bulletin 2001-16 requires an inspection of the hot work area 4 hours after the work is finished.

  22. السؤال 22 من 25

    If combustible materials cannot be moved away from hot work, how far around the work must they be protected from ignition under the bulletin?
    أظهر الإجابة

    الإجابة: D. Within 15 m

    Bulletin 2001-16 says combustible and flammable materials within 15 m must be protected from ignition.

  23. السؤال 23 من 25

    What fire equipment must be in the hot work area under the hot work bulletin?
    أظهر الإجابة

    الإجابة: B. At least one portable fire extinguisher

    Bulletin 2001-16 requires at least one portable fire extinguisher in the hot work area.

  24. السؤال 24 من 25

    On a fire watch with the alarm out of service, you find smoke coming from a storage room. What should you do first?
    أظهر الإجابة

    الإجابة: B. Warn the occupants and call 911 from a safe place

    With the alarm out of service, the fire watch must warn occupants and call 911 right away. Fight a fire only if it is small, you are trained and it is safe.

  25. السؤال 25 من 25

    You missed one hourly round because you were helping an injured person. How should the sign-off sheet show this?
    أظهر الإجابة

    الإجابة: B. Record what really happened and the real time

    The sign-off sheet must show when each patrol was really done. A false entry hides a gap in protection and can be used as evidence against you.

ما يجب معرفته قبل الاختبار

  • New Brunswick adopts the National Fire Code of Canada 2020 through Regulation 82-20 under the Fire Prevention Act.
  • The 2020 code amendments took effect in New Brunswick on May 1, 2025.
  • A sprinkler or alarm system under modification needs a dedicated, 24 hour per day fire watch with hourly patrols.
  • Tampering with alarms, sprinklers or extinguishers without written authorization is an offence under the Fire Prevention Act.
  • A hot work fire watch lasts during the work and 60 minutes after, with an inspection 4 hours after.

الأسئلة الشائعة

How often do I patrol on a fire watch in New Brunswick?

The Office of the Fire Marshal's Technote 2006-09R requires hourly patrols of the areas where the alarm or sprinklers are not working. Follow your post orders if they ask for more.

Can I do other duties during a fire watch?

No. Technote 2006-09R says the fire watch is done by people whose only job is the fire watch.

Who enforces the fire code in New Brunswick?

The fire marshal and the Office of the Fire Marshal, with deputy fire marshals, fire prevention officers and local assistants, who are often fire chiefs.

Is a fire watch needed while the contractor is working on the alarm?

Not always. Technote 2006-07R says no fire watch is needed during the contractor's work day if their staff are always in the affected area and the sprinklers stay fully working and monitored.

هل الشهادة معتمدة أو معترف بها رسميًا؟

لا. إنها شهادة إتمام خاصة للمعرفة فقط. وهي غير معترف بها أو معتمدة أو موافق عليها من أي حكومة أو جهة ترخيص أو هيئة تنظيمية أو مؤسسة تعليمية، ولا تحل محل أي رخصة أو شهادة أو تدريب يفرضه القانون.

المصادر

اختبارات ذات صلة