EPA Section 608 Certification Practice Test 2026: Practice test 3
Practice test 3 of 3 for the EPA Section 608 Certification Practice Test: 25 more questions with answers and explanations.
-
Question 1 of 25
Show answer
Answer: B. 15 inches of Hg vacuum
Table 1 requires 15 inches of Hg vacuum for medium-pressure appliances of 200 pounds or more with recovery equipment made on or after November 15, 1993.
-
Question 2 of 25
Show answer
Answer: A. 0 psig
For non-major repairs not followed by evacuation to the environment, medium-, high- and very high-pressure appliances must be brought to no higher than 0 psig.
-
Question 3 of 25
Show answer
Answer: A. Removing the compressor, condenser, evaporator or auxiliary heat exchanger coil
EPA defines major maintenance, service or repair as work that involves removing the compressor, condenser, evaporator or auxiliary heat exchanger coil.
-
Question 4 of 25
Show answer
Answer: D. 15 pounds
Section 82.156 limits system-dependent recovery equipment to appliances with a full charge of 15 pounds or less, unless it is a permanent pump-out unit.
-
Question 5 of 25
Show answer
Answer: D. 50 pounds or more
Section 82.157 applies to appliances with a full charge of 50 or more pounds of class I or class II refrigerant, or a blend containing one.
-
Question 6 of 25
Show answer
Answer: C. 20 percent
The trigger leak rate for commercial refrigeration, such as supermarket and cold storage systems, is 20 percent over a 12-month period.
-
Question 7 of 25
Show answer
Answer: C. 30 days
Owners must repair leaks within 30 days, or 120 days when an industrial process shutdown is needed to make the repair.
-
Question 8 of 25
Show answer
Answer: C. Within 10 days
Section 82.157 requires both an initial and a follow-up verification test, and the follow-up test is due within 10 days of a successful initial test.
-
Question 9 of 25
Show answer
Answer: A. Quarterly, until four quarters in a row are below the trigger rate
Commercial and industrial process systems with 500 or more pounds need quarterly leak inspections until four consecutive quarters show leaks below the trigger rate.
-
Question 10 of 25
Show answer
Answer: A. Type III
EPA says Type III certification is for servicing or disposing of low-pressure appliances, such as many centrifugal chillers.
-
Question 11 of 25
Show answer
Answer: C. R-123
Section 82.152 lists R-11, R-123, R-113 and R-245fa as examples of refrigerants used in low-pressure appliances.
-
Question 12 of 25
Show answer
Answer: C. Its refrigerant has a saturation pressure below 45 psia at 104 degrees F
Section 82.152 defines a low-pressure appliance as one using a refrigerant with a liquid phase saturation pressure below 45 psia at 104 degrees F.
-
Question 13 of 25
Show answer
Answer: B. 25 mm Hg absolute
Table 1 of section 82.156 requires low-pressure appliances to be evacuated to 25 mm Hg absolute, whatever the age of the recovery equipment.
-
Question 14 of 25
Show answer
Answer: B. No higher than 0 psig
Section 82.156 says low-pressure appliances must be pressurized to no higher than 0 psig before opening for a non-major repair.
-
Question 15 of 25
Show answer
Answer: D. Use heat first, then nitrogen may bring it up to atmospheric pressure
For refrigerants that boil above 85 degrees F, the rule calls for heat to raise internal pressure first, then nitrogen may be used to reach atmospheric pressure.
-
Question 16 of 25
Show answer
Answer: D. Nitrogen or other methods that need purging afterward
For refrigerants that boil at or below 85 degrees F, section 82.156 says not to use nitrogen or similar methods that would need to be purged later.
-
Question 17 of 25
Show answer
Answer: A. Air conditioning that cools occupied buildings, such as chillers and rooftop units
Section 82.152 defines comfort cooling as air-conditioning appliances that cool occupied facilities, including chillers, split systems and rooftop units.
-
Question 18 of 25
Show answer
Answer: A. 10 percent
Section 82.157 sets a 10 percent trigger leak rate for comfort cooling appliances, the lowest of the three main sectors.
-
Question 19 of 25
Show answer
Answer: C. 30 percent
Industrial process refrigeration, such as chemical plant or ice rink systems, has a 30 percent trigger leak rate over 12 months.
-
Question 20 of 25
Show answer
Answer: B. Report it to EPA by March 1 of the next year
Section 82.157 treats these as chronic leakers, and the owner must report them to EPA by March 1 of the following year.
-
Question 21 of 25
Show answer
Answer: B. Annually, until one year shows leaks below the trigger rate
For comfort cooling and other appliances, section 82.157 requires annual leak inspections until one year passes below the trigger rate.
-
Question 22 of 25
Show answer
Answer: B. Parts of the system run below atmospheric pressure, so air and moisture can leak in and must be removed
Low-pressure systems can operate in a vacuum, so air and moisture leak in, and EPA's Type III topics cover the purge unit that removes them.
-
Question 23 of 25
Show answer
Answer: C. Refrigerant vapor, then liquid
EPA's Type III topics say to introduce vapor before liquid, because liquid at very low pressure can boil and freeze the water in the tubes.
-
Question 24 of 25
Show answer
Answer: A. To drive refrigerant out of the oil so less refrigerant is lost
EPA's Type III topics include heating oil before removal, which releases refrigerant dissolved in the oil so it can be recovered.
-
Question 25 of 25
Show answer
Answer: B. R-123
EPA's Type III test topics list ASHRAE Standard 15 equipment room rules, including a sensor requirement for R-123.
Keyboard: 1–4 to answer, Enter for the next question.