Newfoundland and Labrador Fire Watch Course 2026
This course is for security guards in Newfoundland and Labrador who are posted on a fire watch when a fire alarm or sprinkler system is out of service, or during hot work. It covers the Fire Protection Services Act and Regulations, who enforces them, the notice and hourly patrol rules, fire safety plans and hot work.
En bref
Ce cours gratuit comprend environ 30 minutes de leçons et un test de 25 questions. Obtenez 80 % ou plus pour télécharger une attestation de réussite (privée, non accréditée). Vérifié à partir des sources officielles le 12 octobre 2026.
Ce que vous allez apprendre
- Name the NL fire law, the codes it adopts and who enforces them
- List the steps NL requires when a fire alarm or sprinkler system is shut down
- Patrol at least hourly and keep an accurate fire watch log
- Explain the parts of a fire safety plan and the fire emergency organization
- Respond safely if you find fire or smoke
- Apply the NL OHS rules for hot work
Obtenez 80 % ou plus pour télécharger votre certificat.
-
Question 1 sur 25
Voir la réponse
Réponse: B. The Fire Protection Services Act
The Fire Protection Services Act (SNL 2008, c. F-11.01) provides for the appointment and duties of the fire commissioner.
-
Question 2 sur 25
Voir la réponse
Réponse: D. The National Fire Code of Canada and NFPA 101
Section 3(1)(b) of the regulations adopts the National Fire Code of Canada and the NFPA 101 Life Safety Code for the use and operation of buildings.
-
Question 3 sur 25
Voir la réponse
Réponse: D. 6 months after they are published
Section 3(1.1) says amendments and further editions of the adopted codes are adopted 6 months following publication.
-
Question 4 sur 25
Voir la réponse
Réponse: D. The St. John's Regional Fire Department fire chief
Section 35 of the Fire Protection Services Act gives the fire commissioner's duties in that area to the department's fire chief.
-
Question 5 sur 25
Voir la réponse
Réponse: D. Post a fire watch at the property
Section 10(1)(b) lets the commissioner or a designate post a fire watch to remove or reduce an immediate threat to life.
-
Question 6 sur 25
Voir la réponse
Réponse: A. The fire department and the monitoring station
Section 8(7)(a) requires immediate notice to the fire department and the monitoring station.
-
Question 7 sur 25
Voir la réponse
Réponse: D. When it is expected to last more than 24 hours
Sections 8(7)(a) and 14(3)(a) require written notice when the shutdown is expected to last more than 24 hours.
-
Question 8 sur 25
Voir la réponse
Réponse: C. On all floors, by elevators and at entrances
Section 8(7)(b) requires notices on all floors by elevators and at entrances.
-
Question 9 sur 25
Voir la réponse
Réponse: B. At least once every hour
Sections 8(7)(c) and 14(3)(c) require the area to be patrolled at least once every hour.
-
Question 10 sur 25
Voir la réponse
Réponse: B. The person responsible for the work on the system
Section 8(7) places the duties on the person responsible for completing the work; that person often assigns a guard to patrol.
-
Question 11 sur 25
Voir la réponse
Réponse: B. Notices and hourly patrols, as for a fire alarm
Section 14(3) sets the same steps for fire extinguishing systems as section 8(7) does for fire alarms: notice, posted notices, hourly patrols and notice when the system works again.
-
Question 12 sur 25
Voir la réponse
Réponse: A. Fire department, monitoring station, occupants, owner
Section 8(7)(d) requires notice to the fire department, the monitoring station, the occupants and the owner.
-
Question 13 sur 25
Voir la réponse
Réponse: D. As high priority
Section 8(8) says inoperative systems must be given high priority for repairs to restore full operation.
-
Question 14 sur 25
Voir la réponse
Réponse: B. Meeting any other fire commissioner safety requirements
Section 8(7)(e) requires compliance with any other fire and life safety requirements of the fire commissioner for the shutdown.
-
Question 15 sur 25
Voir la réponse
Réponse: D. An offence
Section 31(d) makes it an offence to interfere with, tamper with or damage installed fire protection or detection equipment.
-
Question 16 sur 25
Voir la réponse
Réponse: C. Section 2.8.2
The procedures refer to National Fire Code Section 2.8.2, Fire Safety Plan.
-
Question 17 sur 25
Voir la réponse
Réponse: B. At least every 12 months
The procedures say the fire safety plan must be reviewed at least every 12 months.
-
Question 18 sur 25
Voir la réponse
Réponse: B. The building Fire Marshal
The procedures describe a building Fire Marshal, supported by deputy fire marshals and floor wardens.
-
Question 19 sur 25
Voir la réponse
Réponse: C. Warn people nearby
The procedures say anyone seeing fire or smoke, or smelling gas, must warn people nearby, then use the nearest manual alarm and call the fire department.
-
Question 20 sur 25
Voir la réponse
Réponse: A. Leave the fire area immediately and close all doors
The card tells people to leave the fire area immediately and close all doors.
-
Question 21 sur 25
Voir la réponse
Réponse: A. Only after tests show it is safe and ignition is controlled
Section 453(1) bars hot work where flammable substances are likely, unless tests show it is safe and procedures control ignition sources.
-
Question 22 sur 25
Voir la réponse
Réponse: A. Ready fire suppression equipment suited to the risk
Section 448 says fire suppression equipment must be readily available and appropriate to the potential loss exposure.
-
Question 23 sur 25
Voir la réponse
Réponse: B. They are repeated at intervals to keep workers safe
Section 453(2) requires tests at intervals to ensure the continuing safety of workers.
-
Question 24 sur 25
Voir la réponse
Réponse: D. Floor wardens
The procedures appoint floor wardens, who make daily visual checks, supervise evacuation and confirm their floor is empty.
-
Question 25 sur 25
Voir la réponse
Réponse: A. Warn people, call 911 and help people get out
With the alarm out, you must warn occupants yourself, call 911 to confirm with the fire department, and help people get out safely.
Clavier : 1–4 pour répondre, Entrée pour la question suivante.
À savoir avant l’examen
- NL's Fire Protection Services Regulations adopt the National Fire Code of Canada and NFPA 101 for the use and operation of buildings.
- When a required fire alarm or sprinkler system is out in an occupied building, the area must be patrolled at least once every hour.
- The fire department and monitoring station must be told immediately, in writing if the shutdown will last more than 24 hours.
- In St. John's, Mount Pearl and contracted areas, the St. John's Regional Fire Department fire chief carries out the fire commissioner's duties.
- Tampering with installed fire protection or detection equipment is an offence under the Fire Protection Services Act.
Questions fréquentes
How often do I patrol on a fire watch in Newfoundland and Labrador?
The Fire Protection Services Regulations require the area to be patrolled at least once every hour while a required fire alarm or sprinkler system is out. Follow any stricter schedule in your post orders.
Who has to call the fire department when a fire alarm is shut down?
The regulations put this on the person responsible for completing the work on the system. They must notify the fire department and monitoring station immediately, and in writing if the shutdown will last more than 24 hours.
Which fire code applies in Newfoundland and Labrador?
The Fire Protection Services Regulations adopt the National Fire Code of Canada and the NFPA 101 Life Safety Code. They name the 2015 and 2018 editions and adopt later editions 6 months after publication.
Who enforces fire safety rules in Newfoundland and Labrador?
The fire commissioner, with local fire chiefs as assistants. In the St. John's Regional Fire Department area, that department's fire chief carries out the commissioner's duties.
L’attestation est-elle accréditée ou reconnue officiellement ?
Non. C’est une attestation de réussite privée, uniquement pour vos connaissances. Elle n’est reconnue, accréditée ni approuvée par aucun gouvernement, organisme de délivrance des permis, autorité de réglementation ou établissement d’enseignement, et elle ne remplace aucun permis, aucune certification ni aucune formation exigés par la loi.