Question 1 of 25
Show answer
Answer: C. 5 psig
EPA says it is a violation to change oil at higher than 5 psig, so the system must be brought down to 5 psig or less first.
-
Question 2 of 25
Show answer
Answer: C. 25
Appendix D to Subpart F says each test includes 25 questions from the core group plus 25 from each technical group being taken.
-
Question 3 of 25
Show answer
Answer: A. 100
Appendix D says a Universal test has 25 core questions plus 75 technical questions, 25 from each of Type I, II and III, for 100 in total.
-
Question 4 of 25
Show answer
Answer: B. 70 percent
Appendix D sets the passing score for the closed-book Type I, Type II, Type III and Universal tests at 70 percent.
-
Question 5 of 25
Show answer
Answer: B. A proctored core test
EPA says Universal certification requires a proctored core test, and core tests taken open-book cannot be used toward Universal.
-
Question 6 of 25
Show answer
Answer: A. A factory-sealed unit with 5 pounds or less of refrigerant
EPA defines a small appliance as fully manufactured, charged and hermetically sealed in a factory with five pounds or less of refrigerant.
-
Question 7 of 25
Show answer
Answer: B. A household refrigerator
EPA lists home refrigerators and freezers, room and window air conditioners and dehumidifiers as examples of small appliances.
-
Question 8 of 25
Show answer
Answer: B. Type I or Universal
Type I certification covers servicing small appliances such as window units, and Universal certification covers all types of equipment.
-
Question 9 of 25
Show answer
Answer: B. 90 percent
With recovery equipment made after November 15, 1993, technicians must recover 90 percent of the charge when the compressor is operating.
-
Question 10 of 25
Show answer
Answer: D. 80 percent
When the compressor is not operating, the rule requires recovery of 80 percent of the refrigerant with equipment made after November 15, 1993.
-
Question 11 of 25
Show answer
Answer: B. 80 percent of the refrigerant
For small appliances, recovery equipment made before November 15, 1993 must recover 80 percent of the refrigerant.
-
Question 12 of 25
Show answer
Answer: C. Evacuate to 4 inches of mercury vacuum
Section 82.156 lets technicians meet the small appliance requirement by evacuating the appliance to 4 inches of mercury vacuum.
-
Question 13 of 25
Show answer
Answer: B. 84 percent
Appendix D sets a higher passing score of 84 percent for Type I tests that use the mail-in format.
-
Question 14 of 25
Show answer
Answer: D. No
Appendix D states that mail-in format Type I tests cannot be used toward a Universal certification.
-
Question 15 of 25
Show answer
Answer: D. Equipment that needs the appliance's own components, such as its compressor, to remove the refrigerant
Section 82.152 defines system-dependent recovery equipment as equipment that needs help from components in the appliance to remove refrigerant.
-
Question 16 of 25
Show answer
Answer: C. The final person in the disposal chain, such as a scrap recycler or landfill owner
EPA says the final person in the disposal chain, such as a scrap metal recycler or landfill owner, must ensure refrigerant was recovered before disposal.
-
Question 17 of 25
Show answer
Answer: C. The name and address of the person who recovered the refrigerant and the date
The signed statement must include the name and address of the person who recovered the refrigerant and the date it was recovered.
-
Question 18 of 25
Show answer
Answer: D. It can break down into toxic products
EPA's Type I safety topics cover the decomposition products formed when refrigerants are exposed to high temperatures, which can be toxic to breathe.
-
Question 19 of 25
Show answer
Answer: D. Type II
EPA says Type II certification is for servicing or disposing of high- or very high-pressure appliances, except small appliances and MVACs.
-
Question 20 of 25
Show answer
Answer: C. R-410A
Section 82.152 lists R-22, R-407A, R-407C, R-410A and R-502 as examples for high-pressure appliances.
-
Question 21 of 25
Show answer
Answer: A. R-23
The rule lists R-13, R-23, R-503, R-508A and R-508B as examples of refrigerants for very high-pressure appliances.
-
Question 22 of 25
Show answer
Answer: D. Its refrigerant has a saturation pressure between 170 and 355 psia at 104 degrees F
Section 82.152 classes an appliance as high-pressure when its refrigerant's liquid phase saturation pressure is between 170 and 355 psia at 104 degrees F.
-
Question 23 of 25
Show answer
Answer: B. Type II
Section 82.161 says people who work on medium-, high- or very high-pressure appliances must be Type II (or Universal) technicians, and R-134a is a medium-pressure refrigerant.
-
Question 24 of 25
Show answer
Answer: A. 0 inches of Hg vacuum
Table 1 of section 82.156 requires 0 inches of Hg vacuum for high-pressure appliances under 200 pounds, with any recovery equipment age.
-
Question 25 of 25
Show answer
Answer: D. 10 inches of Hg vacuum
Table 1 sets 10 inches of Hg vacuum for high-pressure appliances of 200 pounds or more when the recovery equipment was made on or after November 15, 1993.
Keyboard: 1–4 to answer, Enter for the next question.
The real test: 70 percent on closed-book tests; 84 percent on mail-in Type I tests